How Cold Should a Server Room Be? Temperature and Humidity

How cold a server room should be: ASHRAE temperature and humidity ranges.

A server room does not need to be cold. ASHRAE TC 9.9 recommends an air inlet temperature of 18 to 27 °C (64.4 to 80.6 °F) for most IT equipment, with humidity kept noncondensing and within a dew point band. Measure at the front of the racks, where equipment draws air in, not at the thermostat.

The ranges below come from the ASHRAE reference card for its 2015 Thermal Guidelines, also summarized on the reference data page. Check them against what your equipment makers and facility design specify.

What is the ideal server room temperature?

The ideal server room temperature is any inlet temperature inside the ASHRAE recommended range of 18 to 27 °C (64.4 to 80.6 °F). ASHRAE says facilities should be designed and operated to target this range, and it applies to all four air-cooled equipment classes, A1 to A4.

There is no single magic number inside that band, and stability matters as much as the number itself. The figure that counts is the air entering the equipment, so a room that reads 20 °C at the wall can still have racks pulling in much warmer air if hot exhaust is recirculating.

Treat the recommended range as an operating target and the wider allowable range as a tolerance for short excursions. If your room sits outside the recommended band for long periods, that is a design or airflow question for your facilities team, and the server room requirements guide covers the physical side of the room.

Why isn't colder better for servers?

Colder is not better because IT equipment is designed to run across a temperature range, and overcooling buys little extra protection while costing energy. ASHRAE's recommended range starts at 18 °C, so a room held well below that sits outside the band it recommends designing for.

Overcooling also hides airflow faults instead of fixing them. If one rack runs hot, turning the whole room down treats the symptom while the cause, such as missing blanking panels, open floor tiles or blocked cable openings, stays in place.

The better approach is to control where air goes. Separate hot and cold aisles, seal gaps in racks and floors, and keep cables out of the exhaust path. The guide to data center cooling types explains how different cooling systems deliver air, which affects how far you can raise the set point safely.

What humidity range should a computer room have?

ASHRAE expresses computer room humidity mainly as dew point, not just relative humidity. The 2015 recommended envelope runs from a dew point of −9 °C (about 16 °F) to a dew point of 15 °C (59 °F), with relative humidity no higher than 60%.

Dew point measures the actual moisture in the air, while relative humidity changes as the air warms or cools. So the same room reads different relative humidity in the cold and hot aisles, and dew point is the cleaner control.

Too dry raises static risk. ASHRAE's notes say the chance of generating an 8 kV discharge rises slightly at very low humidity, and they call for grounded wrist straps during hardware maintenance and for mobile carts and furniture to be conductive or static dissipative and bonded to ground. The ESD Association publishes the related static control standards. Too humid risks condensation, which every class prohibits. Newer editions of the Thermal Guidelines have been published since 2015, so confirm which edition your facility designs to.

What are the ASHRAE server room temperature standards?

The ASHRAE standard for server rooms is its Thermal Guidelines for Data Processing Environments, written by technical committee ASHRAE TC 9.9. It defines a recommended range for all classes and wider allowable ranges for each equipment class.

Class A1 is a tightly controlled data center with enterprise servers and storage; A2 to A4 allow progressively wider conditions. The figures below are taken from the ASHRAE TC 9.9 reference card for the 2015 guidelines.

ParameterRecommended or limit (2015 card)Why it matters
Inlet dry-bulb, classes A1 to A418 to 27 °C (64.4 to 80.6 °F)The target for design and daily operation
Allowable dry-bulb, class A115 to 32 °C (59 to 89.6 °F)Tolerance for short excursions, not a target
Recommended moisture−9 °C to 15 °C dew point, max 60% RHLimits static risk at the low end and condensation at the high end
Allowable moisture, class A1−12 °C dew point and 8% RH to 17 °C dew point and 80% RHOuter limit equipment is designed to survive
Temperature change, most equipment20 °C in an hour, no more than 5 °C in any 15 minutesSudden swings stress components
Tape media15 to 32 °C, 20 to 80% RH, 5 °C change in an hourTape needs a steadier environment
Power off, installed but not running5 to 45 °C, 8 to 80% RHApplies after unpacking, not during shipping

Where should you measure server room temperature?

Measure server room temperature at the air inlet of the equipment, which is the front of the rack in most layouts. ASHRAE's limits are written in terms of inlet air, so a reading taken at a wall thermostat or in the hot aisle does not tell you whether you are inside the range.

A practical layout places sensors at the front of each rack, or at least at the end and middle of each row, at the top, middle and bottom of the rack face. The top of the rack is often warmest because hot exhaust can curl over the rack tops. Humidity or dew point sensing at a few representative points is usually enough, since moisture spreads more evenly than heat.

Sensors are physical hardware: they are mounted, cabled and labeled like any other device in the rack. Reading the data, setting alarm thresholds and running the monitoring software belong to your IT or facilities team.

How fast can server room temperature change?

For most IT equipment, ASHRAE limits temperature change to 20 °C in an hour and no more than 5 °C in any 15-minute period. Tape is stricter, at 5 °C in an hour. ASHRAE treats these as the difference between the highest and lowest inlet temperature in that window, not as a steady rate.

This matters most during cooling failures and restarts. When a cooling unit trips, inlet temperatures can climb quickly in a dense room, and when it restarts, cold air can drop them just as fast. A room that swings through its range repeatedly is harder on equipment than one that sits a few degrees warmer but stays steady.

Your facilities team should plan how cooling is staged back on after maintenance or an outage. Staging units back gradually, rather than all at once, helps keep the change inside the limit.

What happens to server temperature and humidity during a move?

During a move, equipment leaves the controlled room and travels through docks, trucks and corridors, so it can arrive colder or warmer than the destination room. The risk is condensation: a cold chassis opened in warm, humid air collects moisture on its boards before anyone notices.

That is why equipment should acclimatize in its packaging at the destination before power-on. The hardware acclimatization guide covers how long to wait and how to check for moisture. Note that ASHRAE's power-off range of 5 to 45 °C applies to equipment unpacked and installed but not running; it is not a shipping specification, so follow the equipment maker's storage and transit limits.

For long routes or extreme weather, climate controlled transport keeps the load within a stable band. Once the room is stable and the equipment has acclimatized, physical power-on checks can start; starting systems and confirming they run correctly is your IT team's work.