Types of Data Center Cooling Systems: Air to Liquid

Data center cooling types: CRAC, CRAH, containment, in-row, liquid, immersion.

The main types of data center cooling systems are room-level air cooling with CRAC or CRAH units, hot and cold aisle containment, in-row cooling, rear-door heat exchangers, direct-to-chip liquid cooling and immersion cooling. Air systems cool the room or row; liquid systems remove heat at the rack or the chip, which suits denser equipment.

Many facilities mix several of these, such as room air for network racks and direct-to-chip loops for a GPU cluster. Each type changes how equipment is placed, connected and moved, so know which one your racks depend on before you plan a relocation or install.

How does data center cooling work?

Data center cooling works by moving heat from the IT equipment to somewhere it can be rejected, usually outdoors. Servers draw cool air through the front, heat it, and exhaust it from the rear; the cooling system captures that heat and carries it away by air, water or another fluid.

Every system has the same three parts: something that collects heat near the equipment, a medium that carries it, and plant that rejects it, such as chillers, cooling towers, dry coolers or condensers. Some facilities also use outside air or water directly when the weather allows, often called economizer or free cooling.

What matters to the equipment is the air at its inlet. The thermal guidelines from ASHRAE Technical Committee 9.9 define recommended and allowable envelopes by equipment class, and the recommended range for most classes is 18 to 27°C (64.4 to 80.6°F) at the server inlet, with humidity limits set by dew point and relative humidity.

What are CRAC and CRAH units?

CRAC and CRAH units are the traditional room-level air coolers in a data center. A CRAC (computer room air conditioner) contains its own refrigeration compressor, like a large precision air conditioner. A CRAH (computer room air handler) has fans and a coil fed by chilled water from a central plant.

Both usually sit around the perimeter of the room and push cool air into a raised floor or directly into the aisles. Cool air rises through perforated tiles in front of the racks, passes through the equipment and returns to the units. They suit low and moderate densities and are the default in many older rooms.

For a move, room-level cooling means rack placement matters. Racks have to sit in the planned rows with fronts facing the cold aisle, perforated tiles have to line up with the rack faces, and blanking panels have to fill empty spaces. A rack turned the wrong way can pull in another rack's exhaust.

What is hot and cold aisle containment?

Containment physically separates cool supply air from hot exhaust air so they do not mix. Racks are arranged in rows facing each other, creating cold aisles at the fronts and hot aisles at the rears, and then one of those aisles is enclosed with doors, end panels or a roof.

Cold aisle containment encloses the fronts and fills that space with supply air. Hot aisle containment encloses the rears and ducts exhaust back to the cooling units or a ceiling plenum. Either approach lets the cooling system work more efficiently and helps support higher densities than an open room.

Containment adds physical constraints to an installation. Rack heights and depths need to match the containment system, gaps between racks have to be sealed, and cable openings need brush grommets. Moving a rack into or out of a contained row can mean removing and refitting panels, so include that step in the schedule. The general layout principles for smaller rooms are in server room requirements.

What are in-row cooling and rear-door heat exchangers?

In-row cooling puts cooling units in the rack row itself, between racks, so cool air is delivered close to the equipment and hot air is captured before it spreads. Rear-door heat exchangers replace a rack's back door with a coil that cools exhaust air as it leaves.

Both are close-coupled systems: they shorten the distance heat travels, which suits rows denser than room cooling handles comfortably. Most use chilled water or a similar coolant piped to the unit or door. Some rear doors are passive and rely on the server fans; others add their own fans.

For installation and moves, these systems bring piping into the row. In-row units take up rack positions and need clear access for service. Rear doors are heavy, hinged to the rack and connected by hoses. Disconnecting and reconnecting the water side is work for the facility's mechanical contractor, and doors are often removed and transported separately from the rack.

What is the difference between liquid and air cooling?

Air cooling removes heat by blowing air across components; liquid cooling removes it by circulating a fluid through or around them. Liquids carry far more heat per unit volume than air, so liquid cooling supports much higher rack densities and reduces the fan power needed inside servers.

Direct-to-chip cooling attaches cold plates to the hottest components, usually processors and accelerators, and circulates coolant through them. A coolant distribution unit (CDU) separates the rack loop from the facility water loop. Immersion cooling submerges whole servers in a dielectric fluid, either single-phase, where the fluid stays liquid, or two-phase, where it boils and condenses. The Open Compute Project cooling environments work covers cold plates, CDUs, immersion, door heat exchangers and heat reuse.

Many liquid-cooled servers still need some air cooling for components outside the cold plate. Plan for both when you place equipment.

How do cooling types compare for moves and installs?

Each cooling type brings its own physical considerations.

Cooling typeHow it worksMove or installation considerations
CRAC or CRAH room coolingPerimeter units supply cool air to the room or raised floorRack orientation, tile placement, blanking panels
Hot or cold aisle containmentEnclosed aisle keeps supply and exhaust air apartPanels removed and refitted, gaps sealed, matching rack sizes
In-row coolingUnits between racks cool air close to equipmentUnits occupy rack positions, piping in the row, service access
Rear-door heat exchangerCoil in the rack door cools exhaust airHeavy doors moved separately, hoses disconnected by the mechanical contractor
Direct-to-chip liquidCold plates and a CDU carry heat away from processorsCoolant drained and refilled by the mechanical contractor, quick-disconnects capped
ImmersionServers submerged in dielectric fluidFluid handling, tank weight, servers drained before transport

Liquid-cooled moves need the most coordination. Relocating liquid-cooled racks sets out the sequence, and relocating GPU and AI clusters covers the dense racks that usually carry these systems.

What are data center cooling requirements for moving equipment?

The cooling requirement for a move is simple to state: the destination must be able to remove the heat your equipment will produce, in the places it will sit, before power-on. Confirm capacity per rack and per row, the cooling type serving each position, and any liquid connections.

Three physical steps follow. First, fluids. Coolant, refrigerant and immersion fluid are handled by the mechanical contractor, and refrigerant work falls under the EPA Section 608 rules for certified technicians; the detail is in refrigerant and coolant handling during decommissioning. Second, placement. Racks go into their planned positions with the right orientation, containment refitted and liquid connections ready for the contractor. Third, acclimatization. Equipment that arrives cold or from a humid truck needs time to reach room conditions before power-on to avoid condensation; hardware acclimatization before power-on explains how to plan that time.

Once equipment is placed and physically checked, your IT team brings systems online and watches temperatures from there.